ABX Water to Air

Description

ABX Range - Air Blast Cooler - Water to Air

AB45 Oil Air X-Ray Cooling Sytem B GrndOur range of x-ray tube cooling systems have been specially adapted for x-ray tube cooling applications, they can also be used for cooling other applications where heat removal is required, but the coolant temperature can be above ambient.

The ABX range of x-ray tube coolers are compact, self-contained units capable of providing water at nominally 5 to 10 ⁰C above ambient and at constant pressure. They incorporate a high pressure pump, analogue pressure gauge, coolant reservoir, digital temperature controller and a thermostatically controlled fan. Standard safety interlocks designed to protect the x-ray tube, include coolant over temperature, low level and low flow, all communicated via volt free contacts, which are monitored by the customer.

Standard units can be adapted further to suit individual requirements.

Standard features

  • Non ferrous coolant circuit.
  • Low coolant flow signal
  • Low coolant level signal
  • Over temperature signal
  • Digital temperature display
  • Analogue pressure gauge
  • On/off fan control
  • Coolant safety by-pass.
  • Supplied complete with circuit breakers and on/off switches.
  • Fan and coolant pump starting contactors.
  • Fan and coolant pump motor protection.
  • IP54 protection.
  • 24 V control circuit where fitted.
ModelCooling Duty*Max. PressurePump FlowTank VolumePowerDimensionsNoise**
-kWbarL/minLV; HzmmdB (A)
ABX10-W-CB-D1.07.055230; 50/60404 x 498 x 35458
ABX30-W-CB-D3.07.06.09.0230; 50/60494 x 597 x 45458
ABX50-W-CB-55.07.07.09.0230; 50600 x 750 x 60050

* delivery temperature @ 10°C above ambient. ** measured @ 1 meters