Process Thermostats » Integral T

Pumps

Integral T: T1200 to T2200

There is always the right Integral for the most varied tasks. All Integral process thermostats offer high temperature stability. They are also available in water-cooled version (W). The units differ according to their cooling, heating and pump capacities. The T1200 and T2200 process thermostats both have a 3.2 bar pump and are both distinguished by having a cooling capacity of 1.2 to 2.7 kW respectively.

Technical features Units T1200 T1200 W T2200 T2200 W
Working temperature range °C -25...120* -25...120* -25...120* -25...120*
Temperature stability ± °C 0.2 0.2 0.2 0.2
Heater power kW 2.25 2.25 2.25 2.25
Cooling output at 20°C kW 1.2 1.6 2.2 2.7
Pump pressure max. bar 3.2 3.2 3.2 3.2
Pump flow max. L/ min 40 40 40 40
Internal volume L 3...7 3...7 3...7 3...7
230V; 50Hz   Yes Yes Yes Yes
208...230V; 60Hz   Yes Yes Yes Yes

* Optional unto 150°C.

Integral T: T4600 to T10000

Two pumps for more performance. The more powerful T 4600 up to T 10000 W Integral process thermostats have a second pump, alongside the existing powerful circulation pump, which provides internal circulation through an external plate heat exchanger, thus enabling efficient, space-saving cooling. In this way, a cooling performance from 4.6 up to 13 kW at 20 °C, with minimal thermal ballast, is achieved. For these units we recommend the use of water / glycol mixtures as a bath liquid. The Thermostats can also be supplied with water-cooled condenser.