Circulation Chillers » Stand-alone Units

CH Range - 6 to 50 kW

Description

CH Range: Air Cooled Refrigerated Circulation Chillers 6 to 50 kW 5 °C to 25 °C

The industrial range of heavy duty CH circulation chillers provides the perfect solution to applications involving high heat removal and coolant flow requirements.

Units are supplied as standard with an impressive array of safety features and are suitable for indoor and outdoor location.

Applications

  • HF generators
  • Resistance welding machines
  • Lasers
  • Central cooling systems
  • Autoclaves
  • MRI scanners
  • Vapor degreasing

Standard features

  • Models are supplied complete with fused circuitry, motor protection, on/off switches and warning indicators
  • Low coolant signaling
  • Coolant flow signaling
  • Refrigeration fault signaling
  • Coolant safety bypass

Options

  • Full ranges of fail-safe process machine interfacing devices are available on request
  • Frost protection package
  • Full weatherproof enclosure
  • Non-standard voltages and frequencies
  • High ambient version
Technical features Units CH60 CH80 CH120 CH160
Product Code   10-104 10-105 10-106 10-107
Capacity at 27°C ambient
Water temperature of 15°C kW 6.4 8.3 12.5 16.3
Water temperature of 10°C kW 5.5 7.2 10.7 14.2
Water temperature of 5°C kW 4.6 6.0 8.7 11.6
Water temperature of 0°C kW 3.7 4.9 6.9 9.4
Capacity at 32°C ambient
Water temperature of 15°C kW 5.8 7.6 11.7 15.0
Water temperature of 10°C kW 5.0 6.6 9.8 13.1
Water temperature of 5°C kW 4.2 5.5 8.0 10.6
Water temperature of 0°C kW 3.4 4.5 6.3 8.6
Maximum heat rejection kW 9.1 11.7 16.0 21.0
Compressor: Nominal rating kW 1.75 2.25 3.0 3.7
Cooling fan air flow at 1450rpm m³/sec 0.57 0.57 1.31 1.43
Pump pressure bar 3 3 3 3
Pump flow min. L/ min 25 25 35 45
Bath volume approx. L 70 70 110 110
Size W/D/H mm 800x680x1431 880x680x1431 980x830x1461 980x830x1581
Technical features Units CH200 CH240 CH330 CH400
Product Code   10-108 10-109 10-115 10-110
Capacity at 27°C ambient
Water temperature of 15°C kW 20.0 24.6 32.5 40.9
Water temperature of 10°C kW 17.3 21.3 27.4 34.3
Water temperature of 5°C kW 14.4 17.5 22.8 28.7
Water temperature of 0°C kW 11.8 14.2 18.5 23.6
Capacity at 32°C ambient
Water temperature of 15°C kW 18.4 22.1 30.8 37.6
Water temperature of 10°C kW 15.9 19.2 25.2 31.5
Water temperature of 5°C kW 13.2 15.7 21.0 26.4
Water temperature of 0°C kW 10.8 12.8 17.0 21.7
Maximum heat rejection kW 25.5 31.0 40.0 50.0
Compressor: Nominal rating kW 4.85 6.3 7.5 9.7
Cooling fan air flow at 1450rpm m³/sec 1.57 2.1 2.56 2.73
Pump pressure bar 3 3 3 3
Pump flow min. L/ min 55 65 100 120
Bath volume approx. L 180 180 180 180