Fan Coil Heat Exchanger - Tube-fin heat exchanger/fan assembly for removing process heat from circulating coolant.
The ALR range of air to liquid heat exchangers offers an ultra clean, stainless steel coolant circuit suitable for high purity deionised water.
Our tube-fin heat exchangers consist of stainless steel tubes expanded into copper fins and provide flexibility to meet a wide range of applications including water-cooled medical and industrial laser equipment. In addition to the standard modules, a computer aided design facility provides the ability to meet specific performance and dimensional requirements.
For Laser Industry and other Medical and Scientific applications.
| Model number (Units) | ALR1-1S | ALR1-1D | ALR2-2S | ALR2-2D | ALR3-1-4P | ALR3-1-2P | ALR4-2-4P | ALR4-2-2P |
|---|---|---|---|---|---|---|---|---|
| Heat dissipation* (Watts) | 300 | 480 | 900 | 1100 | 750 | 1100 | 1700 | 2300 |
| Airflow (l/sec) | 60 | 90 | 120 | 180 | 100 | 170 | 210 | 350 |
| Fluid flow (l/min) | 1.2 | 1.8 | 3.0 | 4.3 | 3.0 | 4.2 | 6.0 | 9.0 |
| Fluid pressure drop (kPa) | 1 | 1 | 3 | 6 | 3 | 5 | 15 | 27 |
| No. of fans | 1 | 2 | 2 | 4 | 1 | 1 | 2 | 2 |
| Fan speed (rev/min) | 2800 | 2800 | 2800 | 2800 | 1400 | 2800 | 1400 | 2800 |
| Full load current (amps) | 0.3 | 0.6 | 0.6 | 1.2 | 0.25 | 0.3 | 0.5 | 0.6 |
| Nominal coil size H x W (mm) | 180x180 | 180x180 | 180x360 | 180x360 | 240x240 | 240x240 | 240x480 | 240x480 |
| Connections (plain tails) | ½" | ½" | ½" | ½" | ½" | ½" | ½" | ½" |
| Noise level (dB(A)) | 50 | 53 | 53 | 55 | 45 | 62 | 50 | 65 |
| Net weight (approx.) (kg) | 4 | 5 | 7 | 9 | 6 | 6 | 12 | 12 |
* Heat dissipation with air/water at 10°C DT
Electrical data: Full load current, 1 phase+N+E at 230V dual frequency 50/60Hz +/-10%
All performance information calculated at 50Hz. 60Hz available on request